Closed  cooling  tower  need  to  consider  the  problem  of  anti-freezing .

           1. If  the  closed  cooling  tower  does  not  need  to  be  operated  in  winter , the  spray  water  and  internal  circulating  water  must  be  drained  in  the  winter  when  it  is  basically  not  used . It  is  recommened  to  use  compressed  air  to  force  the  internal  circulating  water  with  a  pressure  greater  than  4 kg , and  it  is  not  recommended  to  use  carbon  steel  tube  heat  exchangers  for  drainage .

           2. Anti-freezing  operation  in  part  time .

               The  antifreeze  problem  of  the  spray  water  system  usually  adds  an  electric  heater  to  the  water  tray , which  uaually  turns  on  when  the  spray  water  is  below  5  degrees  Celsius  and  stops  above  8  degrees  Celsius . The  temperature  probe  transmits  the  signal  to  the  control  cabinet  and  antomatically  controls  the  start  and  stop  of  the  electric  heater . The  power  selection  of  the  electric  heater  is  determined  according  to  the  circulating  water  volume  and  the  external  temperature .

           3. Frost  protection  for  year-round  operation .